Q.

In case of single line to ground fault 

  • AAll sequence networks are connected in parallel.
  • BAll sequence networks are connected in series.
  • CPositive and negative sequence networks are connected in parallel.
  • DZero and negative sequence networks are connected in series.
Correct Answer : (B)

All sequence networks are connected in series.

Hints :